Fresh Air Requirement Standard
Fresh Air Requirement Standard , also known as Mechanical Ventilation (see Overview page) is used for calculating air changes, which is used in the Heat Loss and Heat Gains calculations. It also calculates the minimum ventilation flow rate based on various global standards, such as CIBSE, ASHRAE, and Building Regulations, and is used to size ductwork and ensure adequate ventilation in the building.
Infiltration Air Change Rate
Infiltration Air Change Rate (see Overview page) is uncontrolled air leakage through the building envelope measured in air changes per hour and is added onto Fresh Air Requirement, which is used in the heat loss and heat gain calculations.
For Heat Losses / Heat Gains we would consider Total Air = Fresh Air + Infiltration.
For Ventilation Purposes we would only consider Fresh Air Requirements.
District Heating
This selection defines how the diversity in the district heating system is calculated.
If you would like for Diversity / Diversification to be applied, you would have to use Heat Interface Unit Equipment for District Heating.
Duct Sizing Method
Choose between three options for duct sizing:
Maximum Velocity: Ensures the duct does not exceed a set maximum velocity.
Maximum Pressure Drop: Ensures the duct does not exceed a set maximum pressure drop.
Maximum Velocity and Pressure Drop: Ensures the duct does not exceed a set limit on both velocity and pressure drop.
Pipe Sizing Method
Choose between three options for pipe sizing:
Maximum Velocity: Ensures the pipe does not exceed a set maximum velocity.
Maximum Pressure Drop: Ensures the pipe does not exceed a set maximum pressure drop.
Maximum Velocity and Pressure Drop: Ensures the pipe does not exceed a set maximum on both velocity and pressure drop.
Percentage of Ventilation Heat Loss / Heat Gain Recovered
This setting is used when a mechanical ventilation heat recovery (MVHR) system will be on the project but not part of your design. This applies to all rooms in the project.
The total heat loss from air changes is adjusted accordingly by specifying a percentage of heat loss to recover (e.g., 50%).
Note this Setting is overridden if an MVHR system is on the design.
Ambient Temperature
The ambient temperature is used in the pipe heat load calculations.
The ambient temperature is used in pipe heat load calculations, but you can only specify a single value for your heat loadβthereβs no option to differentiate between internal and external temperatures; if this distinction is needed, we recommend selecting an ambient temperature that represents a suitable average for the pipeβs location.
Heat Pump Noise Assessment Criteria
MCS 020 a)
MCS 020
Heat Pump Performance Estimate Standard
MCS 031 Version 3: Utilizes
SCOP(Seasonal Coefficient of Performance)If this option is chosen,
SCOPvalues (usually provided by the manufacturer) have to be entered on theHeat PumpunderEnergytab.
MCS 031 Version 4: Utilizes SPF (Seasonal Performance Factor)
If this option is chosen,
Version 4applies SPF based on flow temperatures outlined by MCS.