🔢 Results

Warnings

Warnings appear as yellow boxes in the design, indicating potential issues that may impact system performance, though they don’t prevent calculations from running.

These alerts help you identify and address issues to optimize your design.

To Review Warnings:

Open the Warnings dropdown to view warnings organized by level.

To Hide Warnings:

Use the Display Warnings checkbox to show or hide all warnings in your layout.

To hide individual warnings, click the Eye icon next to any warning that doesn’t need immediate attention.

To Resolve Warnings:

General

Step-by-step
  1. Zoom in anywhere on the drawing.

  2. Click on the warning in the Warnings dropdown.

    This will take you directly to the part of your design with the warning.

  3. Review the guidance under the Information (i) icon next to the warning to see the issue description and suggested fixes.

  4. Make the necessary adjustments in the Design mode.

  5. Return to Results mode to confirm the warning has been cleared.

Warning: Maximum Pressure Exceeded at Node

To resolve this warning, try a combination of the following:

  • Locate the node where the warning appears.

  • Place a PRV before the node to lower the pressure to acceptable levels.

  • Reduce the pressure at the pump if it’s set too high.

  • Update the inlet pressure settings for the node if needed.

  • Ensure the flow source and floor heights are correctly set, as incorrect inputs may lead to high pressure.



Warning: Maximum Pressure Exceeded

To resolve this warning, try a combination of the following:

  • Find the section where maximum pressure exceeds the limit.

  • Place pressure-reducing valves (PRVs) in the design at key points to reduce pressure.

  • Adjust the pump’s pressure output if it’s too high.

  • Double-check floor heights and flow source details to ensure accuracy.



Warning: Safe Working Pressure Exceeded for Pipe

To resolve this warning, try a combination of the following:

  • Select a pipe material that supports higher pressure from Settings > Systems (you can view their maximum safe working pressure in the Catalog) .

  • Place PRVs in the system to reduce pressure before it exceeds safe limits.

  • Decrease the pump output to reduce pressure in pipes.

  • Ensure floor heights and flow source settings are correct to avoid pressure miscalculations.


Warning: Max Flow Rate Exceeded

To resolve this warning, try a combination of the following:

  • Split the flow load by adding extra mixing valves to share the flow rate.

  • Ensure that connected fixtures and nodes have correct flow values to avoid overloading.


Warning: Unvented Drain Exceeds Max WC Capacity

To resolve this warning, try a combination of the following:

  • Add a vent on the unvented section to handle additional WC capacity.

  • Reorganize the pipework to include a vented connection closer to the WC fixtures.

  • In Settings > Systems, increase the max number of WCs allowed per unvented pipe if applicable.


Warning: Max Unvented Length Exceeded

To resolve this warning, try a combination of the following:

  • Insert a vent near the fixture to reduce the unvented length.

  • Reroute the pipe closer to a vented drain to avoid exceeding the max unvented length.

  • Adjust the max unvented length in Settings > Flow Systems if needed.


Warning: Max Fixtures Per Level Exceeded

To resolve this warning, try a combination of the following:

  • Split fixtures across different stacks or levels to decrease load on a single stack.

  • Increase the max allowance of fixtures per level in Settings > Systems if necessary.


Warning: Pressure Overload

To resolve this warning, try a combination of the following:

  • Place PRVs at key points to reduce the pressure.

  • Adjust pump settings to reduce pressure across the system.

  • Modify the inlet pressure settings for fixtures experiencing pressure overload.

  • Verify floor heights and flow source inputs to ensure accuracy.


Warning: Connect the Fixture to a Flow System

To resolve this warning, try a combination of the following:

  • Connect the fixture to the correct flow system pipe.

  • In the fixture’s properties, enable Allow Other Systems to Connect if needed.

    • If updating multiple fixtures, use the Select Similar option for bulk changes.


Warning: Flow System Not Connected to Plant

To resolve this warning, try a combination of the following:

  • Draw pipes to connect the flow system to the plant.

    • Sometimes it looks like its connected, but the pipe stops just short of where it needs to 

  • In the plant properties, set the appropriate flow systems for inlet and outlet.

  • If the plant doesn’t require a connection, you can choose to hide this warning.


Warning: Update Flow System Settings

To resolve this warning, try a combination of the following:

  • Go to Settings > Systems to modify the pipe sizing table.

  • Minimize the connected load on the pipe to match current system settings.


Warning: Loop in Pipe System Detected

To resolve this warning, try a combination of the following:

  • Locate the loop in your pipe layout.

  • Remove or simplify the loop to eliminate redundancy and ensure a single directional flow.


Warning: Invalid Loop

To resolve this warning, try a combination of the following:

  • Examine pipe connections to identify the loop.

  • Alter the layout to remove the loop and establish a linear path.


Warning: Change the Peak Flow Rate Calculation Method

To resolve this warning, try a combination of the following:

  • Go to Settings > Calculations and select a different flow rate calculation method.

  • Minimize loading units to ensure they stay within the current calculation method's capacity.


Warning: No Suitable Pipe Size

To resolve this warning, try a combination of the following:

  • In Settings > Flow Systems, select a new pipe material that supports higher flow.

  • Adjust the maximum velocity setting to allow higher flow rates.

  • Lower the flow rate connected to the pipe if possible.


Warning: Pressure at Upstream Source Needs Higher Than Downstream

To resolve this warning, try a combination of the following:

  • Adjust the pressure at the upstream regulator.

  • Lower the downstream pressure to balance the system.


Warning: Extrapolated

To resolve this warning, try a combination of the following:

  • Update the method in Settings > Calculations to fit within limits.

  • Decrease the number of connected units to avoid extrapolation.


Warning: Valve in Wrong Direction

To resolve this warning, try a combination of the following:

  • Swap the inlet and outlet connections for proper flow direction.


Warning: Directed Valve Forbidden Here

To resolve this warning, try a combination of the following:

  • Take out any directed valves on the recirculating system and relocate them to the primary flow system.


Warning: Contact Southland Filtration for Advice

To resolve this warning, try a combination of the following:

  • Contact 1800 656 771 for site-specific design and configuration advice.

  • Hide this warning if the RO system sizing is confirmed as correct.


Warning: PRVs Are Forbidden Here

To resolve this warning, try a combination of the following:

  • Place pressure reducing valves (PRVs) on the cold water system or on branch dead legs, avoiding the recirculating system.


Warning: Missing Balancing Valve for Return

To resolve this warning, try a combination of the following:

  • Insert a balancing valve in each hot water loop/circuit from the Valve dropdown.


Warning: Missing Lockshield Valve for Return

To resolve this warning, try a combination of the following:

  • Select a lockshield valve from the Valve dropdown and add one to each heating/chilled water loop.


Warning: Not Enough Pressure

To resolve this warning, try a combination of the following:

  • Include a pump to boost system pressure.

  • Change minimum pipe size and max velocity in Systems if required.


Warning: Target Pressure Is Less Than Half of PRV Inlet Pressure

To resolve this warning, try a combination of the following:

  • Install additional PRVs in series to gradually reduce pressure.

  • Reduce pump pressure if possible.


Warning: Overridden Pipe Diameter Insufficient

To resolve this warning, try a combination of the following:

  • Change the pipe diameter to meet vent size requirements.


Warning: Contact Rheem for Advice

To resolve this warning, try a combination of the following:

  • Consult Rheem for a product specification update if the hot water demand exceeds system limits.


Warning: Pipe Not Connected to Flow Source

To resolve this warning, try a combination of the following:

  • Follow the pipe from the warning area to connect it to a flow source.


Warning: Pipe Higher Than Floor Level

To resolve this warning, try a combination of the following:

  • Lower the pipe height or increase the floor height of the level above.


Warning: Not Connected to Flow System

To resolve this warning, try a combination of the following:

  • Draw a connecting pipe from the node or appliance to the appropriate system.


Warning: Add Flow Source to System

To resolve this warning, try a combination of the following:

  • Add a flow source to the drainage system.


Warning: Isolation Valves Required on Ring Main

To resolve this warning, try a combination of the following:

  • Install at least two isolation valves on the ring main.


Warning: Remove Plant from Flow and Return Pipework

To resolve this warning, try a combination of the following:

  • Move plant components from the return pipework to other system branches.


Warning: Arrangement of Pipework Not Suitable for Calculation

To resolve this warning, try a combination of the following:

  • For cold water systems, add isolation valves to interconnecting pipes.

  • In hot water systems, create orderly branches for loops/circuits.


Warning: Return Pipe Not Connected to Outlet or Return

To resolve this warning, try a combination of the following:

  • Connect return pipe to ensure flow reaches both outlet and return.


Warning: Return Pipe Flow Direction Is Ambiguous

To resolve this warning, try a combination of the following:

  • Install check valves to maintain one-way flow in the return system.


Warning: Return Preheat Loop Detected

To resolve this warning, try a combination of the following:

  • Identify and remove any unintended connections in the preheat system.


Warning: Too Many Diverter Valves

To resolve this warning, try a combination of the following:

  • Only use one diverter valve in reverse return systems.


Warning: Pump Configuration Too Low

To resolve this warning, try a combination of the following:

  • Adjust to a suitable configuration from the suggested settings.


Warning: Pump Cannot Supply Pressure

To resolve this warning, try a combination of the following:

  • Select a model with higher pressure capabilities.


Warning: Non-Suitable Pump Model

To resolve this warning, try a combination of the following:

  • Contact the listed manufacturer for assistance with pump selection.


Warning: Downstream Pressure Is Ambiguous

To resolve this warning, try a combination of the following:

  • Verify downstream pipe layout for valid connections.


Warning: Upstream Pressure Is Ambiguous

To resolve this warning, try a combination of the following:

  • Ensure the upstream pipe system is properly connected and configured.


Warning: Capacity Exceeds Max Available

To resolve this warning, try a combination of the following:

  • Verify capacity specifications with the manufacturer or reduce system capacity.


Warning: Pipe Diameter Exceeds Valve Max Diameter

To resolve this warning, try a combination of the following:

  • Reduce pipe diameter to fit within the valve’s maximum size.


Warning: Preventing Upstream Pump from Reaching Target

To resolve this warning, try a combination of the following:

  • Adjust components to avoid blocking pump pressure.


Warning: Pump Prevented from Reaching Target

To resolve this warning, try a combination of the following:

  • Remove any pressure reducing components in the path of the pump.


Warning: Invalid Cap End

To resolve this warning, try a combination of the following:

  • Attach cap end to a pipe or outlet.


Warning: Fixture Downstream of Balancing Valve

To resolve this warning, try a combination of the following:

  • Relocate fixture upstream of balancing valve.


Warning: Node Downstream of Balancing Valve

To resolve this warning, try a combination of the following:

  • Move node upstream of balancing valve in the system.


Warning: Heat Emitter Connected Wrong Way

To resolve this warning, try a combination of the following:

  • Reverse inlet and outlet connections on the heat emitter.


Warning: Plant Return System Misconfigured

To resolve this warning, try a combination of the following:

  • Check for missing valves or incorrect flow direction in return network.


Warning: CIBSE Diversified Flow Cannot Be Calculated

To resolve this warning, try a combination of the following:

  • Ensure pipes are not interconnected in complex layouts.

  • Use isolation valves to simulate peak scenarios if loops are necessary.


Warning: Multiple Connected Flow Sources

To resolve this warning, try a combination of the following:

  • Ensure only one flow source per system to prevent conflicting pressures.

  • Check the layout for unintended additional flow sources.


Warning: Unbalanced Grills

To resolve this warning, try a combination of the following:

  • Install dampers to manage excessive pressure at the grills.


Warning: Fitting Not Recognized

To resolve this warning, try a combination of the following:

  • Ensure the fitting matches a recognized type.

  • Swap with a standard fitting that can be calculated.


Warning: Bend Too Tight

To resolve this warning, try a combination of the following:

  • Move fittings further apart to allow for a proper bend radius.


Warning: Radiator Model Not Found

To resolve this warning, try a combination of the following:

  • Ensure radiator dimensions and model are correctly entered.

  • If needed, choose an available model from the catalog.


Warning: Radiator Model Rating Insufficient

To resolve this warning, try a combination of the following:

  • Confirm the required heat output for the radiator.

  • Select a model that meets or exceeds required output.


Warning: Duct Size Not Found

To resolve this warning, try a combination of the following:

  • Change to Unrestricted sizing mode in Flow System settings.

  • Lower the flow rate to match available duct sizes.


Warning: Underfloor Heating Insufficient

To resolve this warning, try a combination of the following:

  • Raise the water temperature for increased heat output.

  • Select an underfloor heating option with a higher capacity

.

Warning: Cannot Find Suitable Solution for Underfloor Heating

To resolve this warning, try a combination of the following:

  • Ensure that the mean water temperature and room temperature are within manufacturer specifications.


Warning: Cannot Find Suitable Solution for Underfloor Heating Loop

To resolve this warning, try a combination of the following:

  • Ensure that there is a clear route for the loop from the manifold to the room.


Warning: Missing Loop Spacing

To resolve this warning, try a combination of the following:

  • Enter the correct spacing values for underfloor heating loops.


Warning: Underfloor Heating Floor Temperature Too High

To resolve this warning, try a combination of the following:

  • Reduce the water temperature to prevent excessive floor heat.


Warning: No Suitable Model Found for Manifold

To resolve this warning, try a combination of the following:

  • Ensure manifold specifications meet the loop outlet requirements.

  • Choose a manifold with sufficient outlets for your design.


Warning: Heat Pump System Volume Not Met

To resolve this warning, try a combination of the following:

  • Include a volumiser and specify the required volume in properties.

  • Use larger pipes or add emitters to increase total system volume.


Warning: Heat Pump Flow Exceeded

To resolve this warning, try a combination of the following:

  • Choose a heat pump model capable of handling the flow rate.


Warning: Heat Pump Pressure Exceeded

To resolve this warning, try a combination of the following:

  • Choose a model with a higher pressure capacity.

  • Adjust pressure drop per meter in settings.

  • Install hydraulic separation to manage pressure.


Warning: Pump Configuration Too Low

To resolve this warning, try a combination of the following:

  • Adjust to a recommended configuration.

  • If necessary, consult the pump manufacturer for advice.


Warning: No Pump Can Supply Required Pressure

To resolve this warning, try a combination of the following:

  • Select a model capable of meeting the required duty.


Warning: Non-Standard Pump Selection

To resolve this warning, try a combination of the following:

  • Verify the suitability of the selected pump with the manufacturer.


Warning: Downstream Pressure Ambiguity

To resolve this warning, try a combination of the following:

  • Ensure downstream pipes follow a clear configuration.


Warning: Upstream Pressure Ambiguity

To resolve this warning, try a combination of the following:

  • Adjust upstream pipes for consistent pressure flow.


Warning: Capacity Exceeds Max Available

To resolve this warning, try a combination of the following:

  • Confirm the maximum capacity available for the selected component.

  • Reduce the system load to stay within capacity.


Warning: Pipe Diameter Exceeds Valve Max Diameter

To resolve this warning, try a combination of the following:

  • Adjust pipe diameter to match valve capacity.


Warning: Preventing Pump from Reaching Target

To resolve this warning, try a combination of the following:

  • Adjust or relocate any component blocking pump flow.


Warning: Pump Prevented from Reaching Target

To resolve this warning, try a combination of the following:

  • Ensure that no pressure reducing valves obstruct the pump’s flow path.


Warning: Invalid Cap End

To resolve this warning, try a combination of the following:

  • Attach cap end to a relevant pipe or outlet.


Warning: Fixture Cannot Be Downstream of Balancing Valve

To resolve this warning, try a combination of the following:

  • Position the fixture upstream of the balancing valve.


Warning: Node Cannot Be Downstream of Balancing Valve

To resolve this warning, try a combination of the following:

  • Ensure the node is located upstream of the balancing valve.


Warning: Heat Emitter Connected Wrong Way

To resolve this warning, try a combination of the following:

  • Swap inlet and outlet connections to ensure proper flow direction.


Warning: Plant Return System Misconfigured

To resolve this warning, try a combination of the following:

  • Verify return valves are correctly installed and positioned.


Warning: Multiple Flow Sources Connected

To resolve this warning, try a combination of the following:

  • Confirm only one flow source is connected in each system.


Warning: Grill Needs a Damper

To resolve this warning, try a combination of the following:

  • Install a damper to manage pressure at the grill.


Warning: No Suitable Pump Model Found

To resolve this warning, try a combination of the following:

  • Confirm pump specifications meet system needs.

  • Select a model capable of meeting the required flow and pressure.


Warning: Heat Pump Flow Capacity Exceeded

To resolve this warning, try a combination of the following:

  • Select a heat pump capable of accommodating the required flow.


Warning: Isolation Valves Missing

To resolve this warning, try a combination of the following:

  • Place isolation valves in areas where system branching occurs.


Warning: Duct Size Insufficient

To resolve this warning, try a combination of the following:

  • Adjust duct dimensions or choose unrestricted sizing to accommodate flow.


Warning: Insufficient Loop Coverage for UFH

To resolve this warning, try a combination of the following:

  • Increase underfloor heating loop coverage to meet demand.


Warning: Plant Flow and Return Misaligned

To resolve this warning, try a combination of the following:

  • Ensure plant components are correctly connected to designated flow and return pipes.


Warning: No Flow Detected

To resolve this warning, try a combination of the following:

  • Verify all relevant pipes and components are connected for complete flow.


Warning: Fixture Not Connected to Flow System

To resolve this warning, try a combination of the following:

  • Attach the fixture to a relevant flow system by drawing a pipe to it.

  • If the connection is intentionally omitted, choose to hide the warning.


Warning: Return Pipe Not Connected to Outlet or Return

To resolve this warning, try a combination of the following:

  • Ensure the return pipe is properly connected to an outlet or return.


Warning: Valve in Wrong Direction

To resolve this warning, try a combination of the following:

  • Rotate the valve to match the correct flow direction.


Warning: Directed Valve Forbidden Here

To resolve this warning, try a combination of the following:

  • Directed valves are not permitted on recirculating systems; relocate the valve.


Warning: Arrangement of Pipework Not Suitable for Calculation

To resolve this warning, try a combination of the following:

  • Use isolation valves and mark some as 'closed' to simplify calculations for cold water systems.

  • Ensure that circuits branch off in a uniform order for hot water systems.


Warning: Isolation Valve Required on Ring Main

To resolve this warning, try a combination of the following:

  • Place two isolation valves on the ring main to enable peak scenario calculations.


Warning: Heat Pump System Volume Not Met

To resolve this warning, try a combination of the following:

  • Specify the required volume in the properties by adding a volumiser.

  • Adjust the system to meet volume requirements by increasing pipe size or adding emitters.


Warning: Invalid Cap End

To resolve this warning, try a combination of the following:

  • Connect the cap end to a pipe or inlet/outlet if necessary.


Warning: Unvented Drainage Flow Exceeded

To resolve this warning, try a combination of the following:

  • Install a vent to the system to accommodate additional drainage flow.

  • Adjust pipework to reduce unvented flow.


Warning: Pressure Exceeds Maximum Capacity

To resolve this warning, try a combination of the following:

  • Install a pressure reducing valve to maintain safe pressure.

  • Adjust pump settings to reduce inlet pressure.


Warning: Insufficient Insulation Thickness for Pipe

To resolve this warning, try a combination of the following:

  • Ensure insulation meets minimum thickness requirements in system settings.


Warning: Too Many WC Units on Unvented Pipe

To resolve this warning, try a combination of the following:

  • Attach a vent to the pipe system to support additional WC units.

  • Modify flow system settings to increase the maximum WC units.


Warning: Invalid Loop in Pipe System

To resolve this warning, try a combination of the following:

  • Simplify the loop layout and avoid invalid connections.


Warning: Maximum Stack Load Exceeded

To resolve this warning, try a combination of the following:

  • Connect fixtures to a different stack to reduce load.

  • Increase the maximum stack allowance in settings if possible.


Warning: Maximum Flow Rate Exceeded for Valve

To resolve this warning, try a combination of the following:

  • Distribute flow across additional valves to handle the load.

  • Override the valve's maximum flow rate in properties if appropriate.


Warning: Missing Balancing Valve for Return

To resolve this warning, try a combination of the following:

  • Insert a balancing valve into each hot water loop/circuit with this warning.


Warning: Heat Emitter Misconfigured

To resolve this warning, try a combination of the following:

  • Swap inlet and outlet connections for correct configuration.


Warning: Return Pipe Flow Direction Ambiguous

To resolve this warning, try a combination of the following:

  • Insert a check valve in areas prone to backflow.

  • Arrange pipes in a single direction within return loops.


Warning: Maximum Pressure of Pipe Exceeded

To resolve this warning, try a combination of the following:

  • Lower pressure in the system by adding pressure reducing valves.

  • Choose a material rated for higher pressures.


Warning: Node Cannot Be Downstream of PRVs

To resolve this warning, try a combination of the following:

  • Ensure nodes are not located downstream of pressure reducing valves.


Warning: Maximum Pressure at Node Exceeded

To resolve this warning, try a combination of the following:

  • Include a valve to manage excessive pressure at nodes.

  • Verify flow source and floor level inputs to ensure accuracy.


Warning: Flow Direction Mismatch at Plant

To resolve this warning, try a combination of the following:

  • Ensure the plant's flow and return pipes are correctly aligned.


Warning: Flow System Not Connected to Plant

To resolve this warning, try a combination of the following:

  • Attach the inlet and outlet flow system to the plant.


Warning: Exceeds Maximum Flow Rate for Unvented Pipe

To resolve this warning, try a combination of the following:

  • Include a vent in the system to allow for the additional flow rate.

  • Decrease the number of connected fixtures to bring the flow within limits.


Warning: Exceeds Maximum Length for Unvented Pipe

To resolve this warning, try a combination of the following:

  • Place a vent or vented pipe closer to the fixture to reduce unvented length.

  • Reconfigure pipe routing to meet the maximum length requirements.


Warning: Missing Lockshield Valve for Return

To resolve this warning, try a combination of the following:

  • Place a lockshield valve on each return loop in mechanical (heating/chilled) systems where needed.


Warning: Invalid Loop Detected

To resolve this warning, try a combination of the following:

  • Ensure the loop configuration is valid by eliminating unnecessary connections or cross-links.


Warning: Heat Pump Pressure Exceeded

To resolve this warning, try a combination of the following:

  • Choose a heat pump that can handle the increased pressure.

  • Separate high-pressure and low-pressure systems with hydraulic separation.

  • Slightly lower the pressure drop per meter to bring it within limits.


Warning: Missing Flow Source

To resolve this warning, try a combination of the following:

  • Connect a flow source to the system to enable calculations and ensure proper functionality.


Warning: Too Many Diverter Valves

To resolve this warning, try a combination of the following:

  • Ensure only one diverter valve is used in reverse return systems or non-series-parallel layouts.


Warning: Grill Needs Damper

To resolve this warning, try a combination of the following:

  • Place a damper on the grill to regulate and balance airflow.


Warning: Pressure Exceeds Valve Rating

To resolve this warning, try a combination of the following:

  • Add a valve to reduce the pressure before it reaches the valve.

  • Confirm the system pressure does not exceed the valve rating.


Warning: Duct Size Not Found

To resolve this warning, try a combination of the following:

  • Set the sizing method to Unrestricted in Flow System settings to allow more flexibility.

  • Adjust the flow rate to match available duct sizes.


Warning: Loop Spacing Not Set for Underfloor Heating

To resolve this warning, try a combination of the following:

  • Enter a valid loop spacing for the underfloor heating layout to proceed.


Warning: Missing Pipe System Connection

To resolve this warning, try a combination of the following:

  • Trace the disconnected pipe to locate and complete the connection to the flow source.


Warning: Radiator Model Rating Insufficient

To resolve this warning, try a combination of the following:

  • Choose a radiator model that meets or exceeds the required heat output.


Warning: No Suitable Manifold Model for Underfloor Heating

To resolve this warning, try a combination of the following:

  • Choose a manifold model compatible with the number of loop outlets in the design.

 

Warning: Maximum Flow Rate Exceeded for Plant

To resolve this warning, try a combination of the following:

  • Adjust the design to reduce the flow rate to the plant.

  • Upgrade to a model that supports the higher flow rate if necessary.