Pipes/Ducts
This section details the pipe/duct calculations and how each result is determined.
These calculations are influenced by Methods
, Systems
, the drawing layout, and the Properties
of the Pipes
and the connections to the pipes.
Height Above Floor
The Height Above Floor
refers to the vertical distance of a pipe/duct segment above the floor Level
.
This property is critical for determining the pressure changes within the system due to elevation differences.
Influences of Height Above Floor:
The following influence the Height Above Floor
:
Floor Level Height
: The height of the floor level.Pipe/Duct Segment Elevation: The specific
Height
of the pipe/duct segment above the designated floor level.Equipment/Fixture Connection Heights: Heights of connected
Equipment
,Emitters
,Terminals
, orFixtures
that influence the overall pressure calculation.
Troubleshooting Height Above Floor:
Check
Floor Level
Settings:Ensure the floor levels are correctly set in the project properties.
Verify Pipe/Duct Segment Elevations:
Review the
Height
values of each pipe/duct segment in theirProperties
tab.Confirm they match the intended elevation in the design.
Inspect
Equipment
andFixture
Heights:Ensure connected
Equipment
,Emitters
,Terminals
, orFixtures
have accurate height values defined.
Use
Heat Maps
:Identify areas where height variations may cause significant pressure changes.
Analyze
Design Report
:Export the
Design Report
Spreadsheet and check for anomalies in heights.
Peak Flow Rate (Water)
The Peak Flow Rate
in a domestic water system represents the maximum expected flow rate, calculated as the combined demand across all connected fixtures
and nodes
.
Influences of Peak Flow Rate:
Peak Flow Rate Calculation Method
: This setting specifies the calculation standard or method used to derive the peak flow rate.This setting is defined in
Methods
.Diversification
adjusts flow requirements to reflect realistic peak demand rather than the maximum possible flow for everyfixture
. For example, in a residential system, not all fixtures will be used simultaneously; diversification accounts for this by applying a factor that reduces total calculated demand.
Loading/Fixture Units of Fixtures and Nodes
: Each connectedfixture
ornode
has an assigned loading or fixture unit value, representing its contribution to peak flow based on expected usage.This unit is assigned to each
fixture
ornode
in theDesign
phase.Higher loading units increase the peak flow rate, as these units are summed across all connected fixtures to determine total demand.
Continuous Flow Fixtures/Nodes:
Fixtures
ornodes
that operate with a continuous flow (such as certain medical equipment) that bypassdiversification
. Instead, their flow rates are added directly to the peak flow rate calculation, representing a constant demand that does not vary.Identified as continuous flow within node or fixture properties.
Continuous flow fixtures add directly to the peak flow rate without diversification, ensuring that the calculation fully accounts for constant demands..
Spare Capacity
: An optional setting that adds a percentage increase to the peak flow rate for future demand or unexpected increases. Adding spare capacity ensures the system can handle higher-than-anticipated flows without the risk of undersizing.Configurable in
System Settings
as a percentage added to the final peak flow rate.Spare capacity increases the peak flow rate by a specified percentage, providing a buffer for demand fluctuations or future system expansions.
Peak Flow Rate is crucial for determining appropriate pipe sizing, system pressure requirements, and equipment capacity. By calculating the maximum expected demand, this metric helps ensure that the system can meet peak water requirements without performance issues.
Troubleshooting of Peak Flow Rate:
Review the Water section of
Methods
Review the relevant
Systems
Export a
Design Report
and review all of theFixture/Node
values
Peak Flow Rate (Ventilation)
The Peak Flow Rate
in a ventilation system represents the maximum expected flow rate, calculated as the combined demand across all connected diffusers/grilles
.
Influences of Peak Flow Rate (Ventilation):
[Optional]
Vent Air Changes Rate Standard
: This setting specifies the calculation standard or method used to derive the peak flow rate.This setting is defined in
Methods
.Each room typically has a different minimum ventilation flow rate requirement.
Diffuser/Grille Flow Rate Method
: This defines the flow rate in each specific Diffuser/Grille, and there are the following options available:Manual: Manually select the desired flow rate.
If you are not using h2x for ventilation flow rate calculations (by drawing the building footprint, etc.), then you will need to use this one.
If you have completed your ventilation flow rate requirements in h2x, in addition to manually entering your flow rates, you have the following options:
Share Units
: Distributes the building's total required flow rate evenly among all units.Total building flow rate: 100 GPM
Diffusers: 4
Flow rate per unit: 25 GPM each (even distribution).
Percentage
: Allows you to set a specific percentage of the total building flow rate to allocate.Total building flow rate: 100 GPM
Allocated percentage: 60% to Diffuser A, 40% to Diffuser B
Flow rate: Diffuser A = 60 GPM, Diffuser B = 40 GPM.
Room
: Aligns with the specific flow rate required by each room.Room A requires 30 GPM, Room B requires 20 GPM, Room C requires 50 GPM.
Flow rate aligns exactly with each room's requirement: Diffuser in Room A = 30 GPM, Diffuser in Room B = 20 GPM, Diffuser in Room C = 50 GPM.
Room Size: Matches the required flow rate of each room, and distributes any remaining building flow rate proportionally based on
room area
.Total building flow rate: 120 GPM
Room A = 200 sq. ft., Room B = 200 sq. ft., Room C = 400 sq. ft., Room D = 400 sq. ft.
Base flow rate: Room A = 20 GPM, Room B = 20GPM, Room C = 40GPM.
The shared flow for Room D (40GPM) was distributed proportionally: Room A = 10 GPM, Room B = 10 GPM, and Room C = 20 GPM.
Final flow rates: Room A = 30 GPM, Room B = 30 GPM, Room C = 60 GPM.
Spare Capacity
: An optional setting that adds a percentage increase to the peak flow rate for future demand or unexpected increases. Adding spare capacity ensures the system can handle higher-than-anticipated flows without the risk of undersizing.Configurable in
System Settings
as a percentage added to the final peak flow rate.Spare capacity increases the peak flow rate by a specified percentage, providing a buffer for demand fluctuations or future system expansions.
Peak Flow Rate is crucial for determining appropriate pipe sizing, system pressure requirements, and equipment capacity. By calculating the maximum expected demand, this metric helps ensure that the system can meet peak ventilation requirements without performance issues.
Troubleshooting of Peak Flow Rate (Ventilation):
Review the
Mechanical
section ofMethods
Review the relevant
Systems
Export a
Design Report
and review all of the Diffuser/Grille values
Loading Units/Water Supply Fixture Units
The Loading/Water Supply Fixture Units
represent the expected demand of individual fixtures
or nodes
in a water supply system
. These units form the basis for calculating the system's peak flow rate, reflecting realistic water usage patterns.
Influences of Loading Units/Water Supply Fixture Units:
Assigned Loading/Fixture Units
Each
Fixture
orNode
is assigned a fixture unit value based on the selectedPeak Flow Rate Calculation Method
, based on its expected water demand.Fixtures with higher loading units contribute more significantly to the system's total demand.
Diversification Factors
Diversification
converts the sum of loading/fixture units to reflect realistic peak usage.In systems like residential
Water Supply
, not all fixtures operate simultaneously.Diversification
applies a factor to reduce total demand and prevent oversizing.As the total loading/fixture units increase, the peak flow rate grows, but the rate of increase diminishes due to the decreasing likelihood of all fixtures operating at once.
Total Heat Load (THL)
Total Heat Load (THL)
represents the total amount of heat energy lost or gained within a piping system, typically measured in kilowatts (kW) or British Thermal Units (BTUs).
This calculation quantifies the energy required to maintain the target temperature throughout the system, considering heat transfer
through pipes and connected emitters (in mechanical systems only).
Total Heat Load is critical for accurately sizing the pipework on the recirculation system
Influences of Total Heat Load (THL):
Total Heat Load
is influenced by various settings across several categories, including Pipe Specifications
, Temperature Settings
, Insulation Properties
, System Layout
, and Emitter Connections
(in mechanical systems only).
Pipe Specifications
Pipe Material
: Each material (e.g., copper, PVC, steel) has a unique thermal conductivity affecting the heat transfer rate. For example, copperâs high conductivity results in faster heat loss than less conductive materials.Selected in the pipe material section of the
System Settings
.
Pipe Diameter
: Pipe diameter determines the surface area exposed toambient conditions
, influencing heat transfer rates.Selected based on the parameters in the pipe sizing section of the
System Settings.
Insulation Properties
Insulation Type
: Insulation materials like foam and fiberglass have distinct thermal resistances that affect their ability to retain heat within the pipe.
High-performance insulation materials reduce heat loss efficiently.Selected in insulation specifications of
Systems settings
.
Insulation Thickness
: Insulation thickness increases the thermal resistance, reducing heat transfer rates. Thicker insulation retains heat more effectively.Selected in insulation specifications of
Systems settings
.
Temperature Settings
Outlet Temperature
: The temperature of the fluid as it exits the heating or cooling source. Higher outlet temperatures result in a larger temperature differential between the fluid and surroundings, driving fasterheat loss
.Set in
Outlets
tab in the equipmentâs properties and inSystems Settings
.
Ambient Air Temperature
: The surrounding air temperature impacts the pipe'sheat loss rate
. Lower ambient temperatures increase the temperature differential, causing fasterheat transfer
out of the system.Set in
Methods Settings
.
System Layout
Pipe Lengths
: Thecumulative length
andconfiguration
of the piping impact totalHeat Loss.
Longer pipe runs expose moresurface area
toambient conditions
, increasingtotal heat load
as the fluid travels greater distances.
Connected
Emitters
(FCU
,AHU
,Manifolds
,Radiators
): Emitters extract or release heat from the system, impacting the total heat load on the piping network.
Troubleshooting of Total Heat Load (THL):
Review the
Methods
forambient temperature
Review the
Systems
forpipe
/insulation
details andtemperature
Review the
Equipment
outlet temperatureReview the
Emitter
loadsReview each
Pipe Length
to ensure they are correct
Recirculation Flow Rate
The Recirculation Flow Rate
is the flow rate required to maintain the delta T
temperature throughout the Recirculating System
.
The recirculation flow rate
is derived from the Total Heat Load (THL)
and the difference between the flow/outlet
and return temperatures
(delta T) found in the equipment properties.
Recirculation Flow Rate Formula:
Q = E / (cp Ă ÎT)
Where:
Q = Recirculation flow rate (mÂł/s or ftÂł/s)
E = Heat energy (W or BTU/h)
cp = Specific heat capacity of the fluid (J/kg¡K or BTU/lb¡°F)
ÎT = Temperature difference (K or °F)
Influences of Recirculation Flow Rate:
Temperature Settings
Outlet Temperature
: The temperature of water as it leaves the equipment.Set in
Outlets
tab in the equipmentâs properties and inSystems Settings
Return Temperature
: The temperature of the water when it returns to the equipment.Set in
Outlets
tab in the equipmentâs properties
Water Properties
Specific Heat Capacity of Water
: The energy required to raise the water temperature by one degree. This value is specific to the waterâs temperature and directly affects the recirculation flow rate calculation.
Troubleshooting of Recirculation Flow Rate:
Review the
Total Heat Load
on the systemReview the
Equipment
outlet and return temperature propertiesReview the
Include Pipe Heat Load?
option in the Equipment Outlet tab.
Here you can turn off the pipe heat load from being associated with the pipe sizing, leaving just the emitter heat load on the pipe.
Velocity
Velocity
represents the speed at which fluid
moves through a pipe/duct
, typically measured in meters per second (m/s) or feet per second (ft/s).
Maintaining optimal velocity is crucial for preventing issues like noise, erosion, and excessive Pressure Drop
, as well as ensuring efficient and balanced fluid flow throughout the system.
Influences of Velocity:
Flow Rate
: Velocity is directly proportional to flow rate. As flow rate increases, velocity increases.Internal Diameter (ID)
: Velocity is inversely related to internal diameter. Smaller diameters increase velocity for a given flow rate, as fluid must move faster to pass through the restricted area. Larger diameters reduce velocity, allowing fluid to flow at lower speeds.Maximum Velocity Setting
: The system includes a maximum allowable velocity to prevent excessive speed, which could lead to noise, vibration, and potential pipe/duct erosion over time. Designers can set or adjust this limit based on system requirements and material durability.
Velocity Formula:
v = Q / A
Where:
v = Velocity (m/s or ft/s)
Q = Flow rate (mÂł/s or ftÂł/s)
A = Cross-sectional area (m² or ft²)
Troubleshooting Velocity:
Check if the
pipes/ducts
are sized with a maximum velocity setting by going to theMethods
and confirming that thepipe/duct
sizing method includes "maximum velocity".Review the maximum velocity setting for relevant
pipes/ducts
inSystems
to ensure it meets design requirements.Verify that no
pipe/duct
sizes have been disabled, as this could affect availablesizing
options.Confirm that the "maximum velocity" setting hasnât been overridden on specific
pipes/ducts
by selecting each pipe inDesign
Mode and reviewing itsProperties
.Examine the
Flow Rates
on thepipe/duct
to assess if high flow contributes to excessvelocity
.Review the
Pressure Drop
on thepipe/duct
, depending on thepipe/duct
sizing
method. This can affect the sizing rather than justVelocity
.Look at the
Heat Map
forVelocity
, it could give you a visual indication of high or low areas.
Index Node Path
The Show Index Node Path identifies the specific route from the system's start to an outlet, focusing on the segment with the highest cumulative Pressure Drop
.
This path includes Pipes/Ducts
, Equipment
, changes in height, Valves
, and Fittings
that contribute to the pressure drop.
Influences of Index Node Path:
Flow Source (Water Systems Only)
Pressure
&Height
: The pressure at the start of the systemSet in
Properties
tab in theFlow Source
Pipe/Duct Sizing Settings
Sizing
Parameters: The maximum allowableVelocity
and/orPressure Drop
along thePipes/Ducts
in the systemSet in the
Methods
and theSystems
Valve and Fittings
Pressure Drop
: EachValve
andFitting
adds resistance to the overall pressure drop along the path.Most valves and fittings use industry-standard defaults for resistance (
K
orZeta
values), which are not editable.You can override these in the
Properties
tab if a field is available.
Equipment
Pressure Drop
: In the equipment propertiesSet in the
Properties
of each piece of equipment
Elevation Changes
Pipe/Duct Heights
: Variations in pipe/duct elevation impact pressure. Vertical segments are especially significant in determiningPressure Drop
.Set in the
Properties
of eachDuct/Pipe/Riser
and also theEmitter/Fixture/Equipment
you are connecting to.
Troubleshooting of Index Node Path:
Step | Action | Details |
---|---|---|
1 | Use | Visualize areas with high-pressure drops. |
2 | Inspect the Highlighted Path | Check |
3 | Examine | Enable pressure display for each fitting and identify segments with unusually high-pressure differences. |
4 | Redraw Problematic Segments | If the |
5 | Review | Confirm |
6 | Download the | Look for anomalies or unexpected values, such as unusually high-pressure drops, incorrect |
Index Circuit
The Show Index Node Circuit
identifies the segment within a recirculation system with the highest cumulative Pressure Drop
, focusing on the route between Equipment
and its recirculation path.
This circuit includes Pipes, Equipment, Emitters, Valves, and Fittings that contribute to the Pressure Drop.
Influences of Index Circuit:
Equipment
Pressure Drop
: Defined in theProperties
of eachEquipment
.Set in the equipmentâs
Properties
tab, includingRecirculation
settings.
Pipe Sizing Settings
Sizing Parameters
: The maximum allowableVelocity
and/or PressureDrop
along the pipes in the system.Set in
Methods
andSystems
.
Valves and Fittings
Pressure Drop
: Resistance fromValves
andFittings
adds to the overall pressure drop along the circuit.Most valves and fittings use industry-standard defaults for resistance (K or Zeta values), which are not editable.
You can override these in the Properties tab if a field is available.
Emitters
Pressure Drop: Defined in the Properties of each emitter.
Set in the emitterâs Properties tab.
Troubleshooting of Index Circuit:
Task | Steps |
---|---|
Use | Visualize areas with high pressure drops. |
Inspect the Highlighted Path | Check properties of |
Examine Pressure at Valves and Fittings | Enable pressure display for each |
Redraw Problematic Segments | If |
Review Sizing Parameters | Confirm |
Download the Design Report Spreadsheet | Look for anomalies or unexpected values, such as unusually high drops, incorrect flow rates, or mismatched component parameters. |
Pipe Diameter (ø)
The nominal diameter selected for each pipe based on the design conditions
The Pipe Diameter is influenced by the following properties:
Flow Rate: The pipe diameter is sized based on the calculated flow requirements.
Maximum Velocity and/or Pressure Drop Limits: The maximum allowable velocity and/or pressure drop along the pipes in the system will not be exceeded based on the calculated flow rate
Set in the Methods and the Systems
Enabled Pipe Sizes: System settings control which sizes are available, restricting or enabling diameters based on project requirements.
Confirm that the appropriate pipe sizes are enabled/available in System Settings.
Overridden: The pipe diameter or the pipes maximum velocity/pressure drop setting can be overridden in itâs properties
If any segment of pipe looks high, it is likely due to this
If you want to troubleshoot the pipe diameter, it is recommended to follow these steps:
Review the flow rate
Refer to the flow rate section if you want to modify the flow rate
Review the Pressure Drop and Velocity Limits
You may want to modify these to increase or decrease the pipe size
Increase limits (higher velocity and pressure drop) to decrease pipe size
Decrease limits (lower velocity and pressure drop) to increase pipe size
You can set different sizing methods based on riser, mains or branches
Ensure you have drawn with the correct pipe type, and are updating the System associated
Verify Enabled Pipe Sizes
Confirm that the appropriate pipe sizes are enabled in System Settings.
Note it is the internal diameter that is used in the sizing calculation, not the nominal diameter
Analyze the Design Report
Export the Design Report Spreadsheet and review pipe-related parameters such as flow rates, veliocitties, nd pressure drops .
Use Heat Maps
Visualize areas of high pressure drop or velocity within the system to identify problematic segments.
Internal Diameter (ID)
The Internal Diameter (ID) is the interior measurement of the pipe and is directly tied to the Pipe Diameter result. It determines the flow capacity and resistance within the system.
The internal diameter is influenced by:
Pipe Diameter: The internal diameter is calculated based on the selected nominal diameter.
Pipe Material: Different materials may have slight variations in internal diameter, which are defined in the Catalog.
To trobulehoot the Internal Diameterresult:
Check the Pipe Diameter:
Refer to the Pipe Diameter result section to address related issues such as flow rate, pressure drop, or velocity.
Verify the Catalog Data:
Ensure the internal diameter matches the selected pipe material and size.
System Selection:
Confirm the correct material is selected in the Systems settings.
Duct Sizing
The duct size is determined based on the design conditions and is selected to ensure optimal airflow, efficiency, and pressure control.
The influencing properties of duct sizing are:
Flow Rate
The duct size is determined based on the calculated airflow requirements.
Maximum Velocity and/or Pressure Drop Limits
The maximum allowable velocity and/or pressure drop along the ducts in the system will not be exceeded based on the calculated flow rate.
These settings are configured in the Methods and Systems tabs.
Overrides
Duct size or maximum velocity/pressure drop settings can be overridden in the Properties tab.
If a duct size looks unusual, it may be due to an override in its settings.
To troubleshoot issues with duct sizing, follow these steps:
Review the Flow Rate
Check the flow rate section to ensure the values align with system requirements.
Adjust the flow rate if needed to influence the duct size.
Review Pressure Drop and Velocity Limits
Modify these limits to increase or decrease duct size:
Increase limits (higher velocity and pressure drop) to decrease duct size.
Decrease limits (lower velocity and pressure drop) to increase duct size.
Configure separate sizing methods for System Settings' mains, branches, or risers.
Ensure the duct is assigned to the correct system and matches the intended type.
Analyze the Design Report
Export the Design Report Spreadsheet to review duct-related parameters such as flow rates, velocities, and pressure drops.
Look for discrepancies or unusual values in the duct sizing.
Use Heat Maps
Visualize areas of high-pressure drop or velocity to identify problematic segments.
Check for Overrides
Inspect the Properties tab for any overridden sizes or limits.
Correct overrides if they conflict with the design parameters.
Cross-Sectional Area
The cross-sectional area refers to the internal area of a duct and is directly tied to its dimensions.
The influencing properties of cross-sectional area are:
Duct Dimensions
The area is calculated based on the selected duct dimensions:
For rectangular ducts: width Ă height.
For circular ducts, the internal diameter area is calculated.
To resolve issues with the cross-sectional area, follow these steps:
Check duct dimensions
Review the duct dimensions in the properties tab to ensure they match the design requirements.
For rectangular ducts, confirm both width and height are accurate.
Verify shape selection
Ensure the correct duct shape (rectangular or circular) is selected for each segment.
Check for high aspect ratios in rectangular ducts, which may increase resistance.
Analyze design report
Export the design report spreadsheet to check area values for each duct segment.
Look for discrepancies or unexpected values, such as insufficient area for required airflow.
Use heat maps
Visualize areas of high velocity or pressure drop that may indicate issues with the cross-sectional area.
Redraw segments if necessary
If discrepancies persist, delete and redraw affected duct segments to recalculate the area based on updated dimensions or design inputs.
Pipe/Duct Material
The Pipe/Duct Material refers to the type of material used for the pipe/duct (e.g., copper, steel, PVC), which directly affects flow resistance, heat retention, and pressure tolerance.
The pipe/duct material is influenced by:
System Settings: Materials for risers, mains, and branches are defined here.
Properties Overrides: The material can be overridden in the Properties tab for specific segments.
To troubleshoot the Pipe/Duct Material:
Verify System Settings:
Ensure the correct materials are assigned to System Settings' risers, mains, and branches.
Check Properties:
Inspect the pipe/duct's properties to confirm the material matches your design requirements, as it may have been overridden.
Inspect the Drawing:
Confirm that pipes/ducts are drawn with the correct material type.
If inconsistencies are found, update the associated system in the properties (you can right-click and select similar to select a lot at once) or redraw the segment with the correct material.
Pressure Drop (PD)
The Pressure Drop refers to the total pressure loss across a pipe/duct segment caused by friction as fluid moves through the pipe/duct.
The formula for calculating pressure drop is:
ÎP = f Ă (L / D) Ă (Ď Ă v²) / 2
Where:
ÎP = Pressure drop (Pa or psi)
f = Friction factor (dimensionless, depends on pipe roughness and Reynolds number)
L = Length of the pipe (m or ft)
D = Internal diameter of the pipe (m or ft)
Ď = Fluid density (kg/mÂł or lb/ftÂł)
v = Fluid velocity (m/s or ft/s)
The following properties influence the Pressure Drop:
Flow Rate and Velocity:
Higher flow rates and velocities increase friction, resulting in greater pressure drops.
Managed by adjusting flow rates or selecting a larger pipe/duct diameter.
Pipe/Duct Diameter:
Smaller pipe/duct diameters create more resistance and increase pressure drop.
Larger diameters help reduce pressure drop.
Roughness Coefficient
The material roughness impacts friction:
Rougher materials (e.g., steel) have higher friction coefficients and cause greater pressure drops.
Equation
Calculated using the Darcy-Weisbach equation with the Colebrook-White coefficient.
Factors include flow rate, pipe/duct diameter, material roughness, and fluid density.
To resolve issues related to excessive or insufficient pressure drop, follow these steps:
Check Flow Rate
Review the flow rates in the system to ensure they are correct.
Check Settings
Review the Maximum Velocity and Pressure Drop settings in the Methods and Systems.
Adjust these settings to align with system requirements.
Inspect Pipe/Duct Diameter
Verify that the pipe/duct diameters match the design requirements.
Smaller diameters increase pressure drop; consider selecting larger pipes/ducts for affected segments.
Review Pipe/Duct Material and Roughness Coefficient
Confirm the material selected for each pipe/duct segment:
Rougher materials (e.g., steel) may cause higher friction.
If necessary, replace with smoother materials (e.g., PVC) to reduce resistance.
Analyze the Design Report
Export the Design Report Spreadsheet to check pressure drop values for each segment.
Look for anomalies or areas where pressure drop exceeds design limits.
Use Heat Maps
Visualize areas of high-pressure drop within the system to identify problematic segments.
There may be areas where the maximum limits have been overridden
If you find areas with high-pressure drops are unsure why, delete and redraw the affected pipe/duct segments. Ensure the correct diameter, material, and connections are used.
Verify Connections
Ensure all pipe/duct connections, fittings, and valves are accurately defined and appropriately sized to minimize resistance.
Length
The Length refers to the measured distance of a pipe or duct segment, which is critical for determining pressure drop, velocity, and overall system performance.
The following influence the length:
1. Drawing Scale
Length is automatically calculated based on the scale of the drawing.
If the drawing is not to scale, the calculated length may be inaccurate, leading to incorrect pressure drop and velocity values.
2. Manual Overrides
Length can be overridden manually in the segmentâs Properties tab.
Overrides should only be used when the drawn length does not accurately represent the actual system length (e.g., for hidden segments or prefabricated components).
To resolve issues with pipe or duct segment lengths, follow these steps:
1. Verify the Drawing Scale
Check that the drawing is set to the correct scale.
Use the Scale Drawing Tool to confirm or adjust the scale for accuracy.
2. Inspect Length Overrides
Review the Properties tab for each segment to see if the length has been manually overridden.
If overridden, ensure the manual value matches the actual length of the pipe or duct.
4. Use Heat Maps and Design Reports
Heat Maps: Visualize discrepancies in length-related parameters, such as pressure drop or velocity.
Design Reports: Export the Design Report Spreadsheet and verify the lengths of all segments for anomalies.
5. Redraw Affected Segments
If lengths appear incorrect, delete and redraw the affected segments to recalculate the length based on the updated scale or geometry.
Pressure Drop Rate
The Pressure Drop Rate is the pressure loss per unit length of a pipe segment.
The Pressure Drop Rate is influenced by the following properties:
Pressure Drop
The pressure drop across a segment.
Pipe/Duct Length
The length of the segment
To address issues with high or unexpected pressure drop rates, follow these steps:
Check Total Pressure Drop
Review the total pressure drop for each segment to identify areas with excessive values.
Inspect Pipe/Duct Lengths
Review the length result filters If the length looks unusual, it may have been overridden in the properties